NFPA 72 Chapter 23.10.2 states: “Fire alarm systems used for partial evacuation and relocation shall be designed and installed so that attack by fire within a notification zone shall not impair control and operation of the notification appliances outside that notification zone.” Most, if not all hospitals use partial evacuation or relocation when a fire [Read More]
Archives for 2022
Do fire alarm horns have to be synchronized?
Since 1996, NFPA 72 has required the use of the temporal 3 pattern for the audible fire alarm signal. NFPA 72 Chapter 18.4.2.3 requires the standard temporal 3 evacuation signal to be synchronized within a notification zone. As an example, a zone would be the devices in an apartment corridor. Each apartment would also be [Read More]