Since January 1, 2016 the State of Illinois has required carbon monoxide (CO) detectors in schools which fall under the jurisdiction of the Illinois State Board of Education. Public Act 099-0470 inserted language to 105 ILCS 5/10 that added the requirement for school boards of education to ensure each school has proper CO detection in [Read More]
If an elevator lobby detector activates, can I selectively exclude that lobby and have the cars still run?
Generally, an elevator’s FEO doesn’t allow the cabs to run once activated, so a selective application usually isn’t an option. I say usually because hospitals employ a Code Blue elevator control system to override the elevator FEO in life saving situations. That’s an extra cost on a more robust elevator controller and obviously doesn’t apply [Read More]
Simultaneous Elevator Recall Activation
I recently received a good question through the comment section regarding one of our elevator recall blogs. The question was: Is it proper to use one addressable fire input into an elevator recall point then parallel out of this point into another separate elevator controller recall input? A: If separate controllers handle cars in the [Read More]
Fire Alarm and Emergency Voice System Testing and Inspection
In our last post, we talked about why it’s important to use a third party to test a smoke detector’s sensitivity level. In this post, we’ll cover another area of concern: verification of outputs. In a simple system that just activates the horn/strobes, that may seem to be an easy task. However, there is always more than [Read More]
Testing & Inspecting Fire Alarm & Emergency Voice Systems
A fire alarm system is required to be tested regularly, the results of which are reviewed by the fire department. When scheduling a test of a facility’s fire alarm system, property managers have a vested interest in maintaining safety compliance and limiting their liability exposure while keeping an eye on operating costs. Operating cost reduction might seem [Read More]
Smoke Detector Testing
At Affiliated Fire Systems, we often get asked about a smoke detector’s lifespan . Specifically, when should a building manager replace smoke detectors? There is no hard and fast lifespan for a commercial smoke detector. To be clear, commercial smoke detectors are connected to a fire alarm panel, not the battery operated devices you can [Read More]
Elevator Recall Activation
I recently had a question asked about whether two smoke detectors are required to activate simultaneously in a single elevator lobby in order for cab recall to be initiated. The answer is there is no current national code that requires two detectors to activate before recall occurs. The two detector activation is what we call ‘cross zoning’, and [Read More]
Fire Alarm System Testing & Inspection, Part II
In our last post, we discussed why regular testing and inspection of a facility’s life safe system is both required and in a property manager’s best interest. What, then, should a proper test and inspection consist of? In this post, we’ll address proper smoke detector testing. A true test of a fire alarm system ensures the system will [Read More]
Fire Alarm System Testing & Inspection, Part I
Commercial fire alarm systems are a lot like referees. You really shouldn’t notice them until they are needed. How does a property owner or manager keep it that way, plus know that it will work when needed? A proper test and inspection of the system is the answer. Most municipalities require an annual test and [Read More]
Follow Us!